The primary purpose of adding capillary tubes to a remote seal (often called a double flange) level transmitter is to physically isolate the sensing elements (flanges and diaphragms) from the process medium. This enables accurate and reliable measurement in harsh or demanding applications where direct contact would cause failure. In essence, the flanges sense pressure, the capillaries safely transmit the signal, and the combination enables remote measurement.
1. Primary Purpose: Solving Measurement Challenges in Harsh Process Conditions
A. Measuring High-Temperature Media
· Problem: If the process fluid is very hot (e.g., above 120°C/250°F), the heat can transfer directly to the transmitter's internal sensor (filled fluid and strain gauge). This causes sensor drift, damage, or even vaporization of the fill fluid, leading to complete measurement failure.
· Solution: Long capillary tubes allow the hot process flanges to be mounted on the vessel while the transmitter electronics can be installed in a cooler, remote location. The capillaries act as a heat sink and thermal barrier, protecting the critical sensor.
B. Handling Corrosive, Viscous, or Crystallizing Media
· Problem: Strong acids, alkalis, viscous slurries, or solutions that crystallize can clog, corrode, or contaminate direct-contact impulse lines, ports, and diaphragms.
· Solution: The remote flange diaphragms can be made from special materials (Hastelloy, Tantalum, etc.) for corrosion resistance. Crucially, the capillary system is entirely filled with a stable silicone or fill fluid, completely isolating the medium. The process only contacts the diaphragm, never entering the measurement system, ensuring long-term stability and safety.
C. Meeting Sanitary/Hygienic Requirements (Food, Pharmaceutical)
· Problem: Processes require frequent Clean-in-Place (CIP) or Sterilize-in-Place (SIP) cycles. Measurement equipment must be free of dead legs, easy to clean, and prevent bacterial growth.
· Solution: Sanitary flush flanges with smooth diaphragms are used. The remote seal design allows the transmitter body to be mounted away from the harsh cleaning zones, protecting its electronics from high-pressure steam, water, or cleaning chemicals.
D. Measuring Solidifying or Freezing Media
· Problem: Media that solidify at ambient temperature (e.g., asphalt, sulfur, heavy oils) would block conventional impulse lines.
· Solution: The flanges mount directly on the vessel. If media solidifies, it only forms a layer on the diaphragm surface without blocking the sealed capillary tubes. Pressure is still transmitted accurately via the fill fluid. The flanges and capillaries can also be heat-traced.
2. Key Characteristics and Considerations of Capillary Systems
· Fill Fluid (Silicone Oil): The properties of the capillary fill fluid are critical. Its density and thermal expansion coefficient directly impact measurement accuracy. The correct fluid type (high-temperature, low-temperature, etc.) must be selected based on the process temperature range.
· Temperature Effects: The fill fluid in the capillaries expands and contracts with ambient temperature changes, which can introduce pressure errors. Therefore:
· Capillary length should be minimized (typically under 30 meters / 100 feet).
· Both high- and low-side capillaries must be routed together (bundled) over the same path to ensure they experience identical temperature changes, allowing the thermal effects to cancel out.
· Mechanical Protection: Capillaries are typically armored (stainless steel braid or conduit) to prevent kinking, crushing, or damage from vibration or impact, which would cause system failure.
Comparison with Traditional Impulse Line Installation
|
Feature |
Remote Seal with Capillaries |
Standard Flange or Impulse Lines |
|
Installation |
More complex (routing/securing capillaries) |
Simpler |
|
Maintenance |
Lower (no plugged impulse lines) |
Higher (may require frequent purging, blowdown) |
|
High-Temperature Suitability |
Excellent (transmitter can be remote) |
Poor (sensor directly exposed) |
|
Corrosion Resistance |
Excellent (only diaphragm exposed) |
Fair (impulse lines & sensor need protection) |
|
Clogging Resistance |
Excellent |
Poor (impulse ports easily clogged) |
|
Sanitary/Hygienic |
Excellent |
Fair |
|
Dynamic Response |
Slower (damped by fill fluid) |
Fast |
|
Cost |
Higher |
Lower |
Conclusion
Adding capillary tubes to a remote seal (dual flange) level transmitter is fundamentally an engineering design that trades space for safety and reliability. By introducing the capillary as an "isolation buffer," it accepts a slightly slower dynamic response and higher initial cost. In return, it achieves stable, reliable, and long-term measurement capability in high-temperature, corrosive, clogging, or sanitary applications. This makes it a classic and essential solution in industries like chemical, oil & gas, pharmaceutical, and food processing.